Name Shivam
|
|
|
|
1. Question text:
|
|
Design a system using a conductive water sensor (basically two metal probes that are very close together - when water is present between the probes it conducts) to detect when water level in a tank falls below 20% and when that happens, turn on a pump. The pump is a 3-phase 3-wire 1kW rated. This is for an industrial application where the water is being used for a chemical process. Design the system with some fail-safe such that the tank should never become empty.
|
|
|
|
|
|
2. Design summary:
|
|
Good approach. For reliability it is ok to say good quality components but beyond that how doyou ensure fail safe?
|
|
e.g. one way is to have redundancy - multiple sensors; bakckup alerts, etc.
|
|
for example, what if the relay fails? Or the motor is powered but the pump is blocked etc?
|
|
You need to close the loop from the circuit instructing the motor to be on but pump not working somehow.
|
|
What about over-rides? What if your box fails - is it possible to manually enable/disable the motor if needed?
|
|
|
|
3. Block diagram
|
|
your block diagram is a muddle of electrical, signal and mechanical items. Think a little about how to make a readable and clear diagram
|
|
|
|
4. Power supply design
|
|
Looks like your voltage level diagrams have some mistake. when tank is 100% full, all ABC lines should be ~12V.
|
|
Why are you realising gates through transistors? Can't you just use 74LSxx series chips?
|
|
|
|
5. Industrial Design:
|
|
Could have been more detailed - with mechanical details, specific material etc.s
|
|
|
|
6. KICAD Design
|
|
Schematic:
|
|
Looks good
|
|
|
|
PCB:
|
|
No PCB Found. I've deducted some points for that but other responses are all ok.
|
|
|
|
7. Pricing / BOM / Assembly
|
|
Why do you need 400V transistors?
|
|
Where are remaining components in the BOM + pricing? Connectors, pcb, etc...?
|
|
|