Name: Rajeevdass 1. Question text: Design a system using the humidity sensor (https://drive.google.com/file/d/10Z0jvXlMJBG0_FohJ6fIrFQnS-VmN8HF/view?usp=sharing) to detect when relative humidity (RH) in a room goes outside the "normal" range of 30%-60%. When RH is outside the "normal" range, a buzzer should sound The device is intended for a controlled-environment room that contains several rare medicinal plants. Any long term (more than a 2 hours) deviations in humidity will kill the plants causing losses of at least 100,000$. A facilty manager is supposed to turn on a humidifer or de-humidifier as required when alerted by this device. 2. Design summary: Could have added more details. Adding temp is a good idea, but what about the original problem of reliability / fail safe? 3. Block diagram A uC cannot drive the buzzer directly normally, The block diagram should have much more details, at least at a high level. Also signal types, levels, widths, etc. 4. Power supply design None submitted 5. Industrial Design: 6. KICAD Design Schematic: PCB: 7. Pricing / BOM / Assembly